Energy Conservation Measure
GSHP with DOAS (More Design Parameters)
Type
UID
c512fb7e-8d46-4889-b3af-7c9b16ae36a6
Version ID
78a2d390-e1be-4426-94df-879120081431
Attributes
| Measure Type | ModelMeasure |
| Uses SketchUp API | false |
Details
| Description | Measure replaces existing HVAC system (if any) with a Ground Source Heat Pump (GSHP) with DOAS HVAC system (one DOAS per floor). The GSHP with DOAS system (centralized DOAS, with zone level conditioning) is applied to all space types except storage spaces like stairwells, mechanical/electrical rooms etc. | |
| Modeler Description | Airloops are dedicated to ventilation (DOAS) and have constant or variable speed fan operation, gas furnace heating,single speed DX cooling and optional energy recovery and/or direct evaporative cooling. Conditioning is provided at the zone level with water sourced heat pumps with cycling fans. The heat pumps are connected to a plant loop supplied by a boiler and cooling tower. The heat pump loop floats between 70F and 90F. | |