Energy Conservation Measure

Air Handling Unit Fan Motor Degradation

Name 
air_handling_unit_fan_motor_degradation
Display Name 
Air Handling Unit Fan Motor Degradation
UID
9814a5e9-37b7-472a-bae5-e9e2e794c024

Version ID
f7a5563f-691d-431c-9f1f-57bf2fb26bf2
Class Name 
AirHandlingUnitFanMotorDegradation
Version Modified 
20180828T214729Z
Schema Version 
3.0
Rating 
0
No votes yet
Attributes 
Measure TypeEnergyPlusMeasure
Intended Software ToolOpenStudio Application
Intended Software ToolParametric Analysis Tool
Intended Software ToolAnalysis Spreadsheet

Details

DescriptionFan motor degradation occurs due to bearing and stator winding faults, leading to a decrease in motor efficiency and an increase in overall fan power consumption. This measure simulates the air handling unit fan motor degradation by modifying either the Fan:ConstantVolume, Fan:VariableVolume, or the Fan:OnOff objects in EnergyPlus assigned to the ventilation system. The fault intensity (F) for this fault is defined as the ratio of fan motor efficiency degradation. This measure was authored by Herrick Laboratory researchers at Purdue University in collaboration with staff from the National Renewable Energy Laboratory. For assistance using this measure please post to https://unmethours.com/questions/
Modeler DescriptionTwo user inputs are required and, based on these user inputs, the fan efficiency is recalculated to reflect the faulted operation as shown below, where η_(fan,tot,F) is the degraded total efficiency under faulted condition, η_(fan,tot) is the total efficiency under normal condition, and F is the fault intensity. η_(fan,tot,F) = η_(fan,tot)∙(1-F)
Files 
ScheduleSearch.rb
measure.rb
OpenStudio 2.4.0
Min Compatible Version: 2.4.0
Max Compatible Version: 2.4.1
LICENSE.txt
Content visibility 
Use group defaults
Download

Measure Arguments

NameDisplay NameShort NameDescriptionUnitsTypeRequiredModel DependentDefault ValueChoicesMin ValueMax Value
fan_choiceEnter the name of the faulted Fan:ConstantVolume, Fan:OnOff object or Fan:VariableVolume. If you want to impose the fault on all fan objects in the building, enter * ALL Fan objects *---Choicetruefalse* ALL Fan objects ** ALL Fan objects *--
eff_degrad_facDegradation factor of the total efficiency of the fan during the simulation period. If the fan is not faulted, set it to zero.---Doublefalsefalse0.15---
sch_choiceEnter the name of the schedule of the fault level. If you do not have a schedule, leave this blank.---Stringfalsefalse----

Measure Outputs