| Name | Zedgk_12_hvac |
| Display Name | Zedg K12 Hvac Gshp With Doas |
| uuid | 59793426-1d07-41d2-9478-d7abf1410764 |
| Type | Measure |
| Language | Ruby |
| Tags | HVAC.Whole System |
| Description | Each zone served by the DOAS (classrooms, corridors, library/media center, lobbies, mechanical rooms, offices, and restrooms) was modeled with a two-speed GSHP. |
| Modeler's Description | The heat pumps rejected energy to a single plant loop that was served by a 90% efficient variable-speed pump with 40 ft of head and a design loop exit temperature set point of 69.8°F. A ground heat exchanger was modeled using the EnergyPlus Runtime Language. The EnergyPlus Runtime Language program raised the temperature of the loop 10°F if the entering water temperature was lower than 60°F, and it lowered the temperature of the loop 10°F if the entering water temperature was higher than 60°F. |
| Uses SketchUp API | false |
| Measure Type | ModelMeasure |
| OpenStudio Version | 2.0.0 |
| Minimum Compatible OpenStudio Version | 2.8.0 |
| README File | View README File |
| GitHub Repo Link | View on GitHub |