Name | Zedgk_12_hvac |
Display Name | Zedg K12 Hvac Gshp With Doas |
uuid | 59793426-1d07-41d2-9478-d7abf1410764 |
Type | Measure |
Language | Ruby |
Tags | HVAC.Whole System |
Description | Each zone served by the DOAS (classrooms, corridors, library/media center, lobbies, mechanical rooms, offices, and restrooms) was modeled with a two-speed GSHP. |
Modeler's Description | The heat pumps rejected energy to a single plant loop that was served by a 90% efficient variable-speed pump with 40 ft of head and a design loop exit temperature set point of 69.8°F. A ground heat exchanger was modeled using the EnergyPlus Runtime Language. The EnergyPlus Runtime Language program raised the temperature of the loop 10°F if the entering water temperature was lower than 60°F, and it lowered the temperature of the loop 10°F if the entering water temperature was higher than 60°F. |
Uses SketchUp API | false |
Measure Type | ModelMeasure |
OpenStudio Version | 2.0.0 |
Minimum Compatible OpenStudio Version | 2.8.0 |
README File | README.md |
GitHub Repo | NREL/openstudio-aedg-gem |